Авторизоваться | регистр
Product
Product

Центр продуктов

дома > Центр продуктов > 10-35KV Vacuum Circuit Breaker > Vacuum Contactor > VKG1-12 Single Pole Contactor for Capacitor Bank

VKG1-12 Single Pole Contactor for Capacitor Bank

    VKG1-12 Single Pole Contactor for Capacitor Bank

    JCZ7(G)12kV 400A Vacuum ContactorThis series of medium-voltage vacuum contactors uses high-quality vacuum interrupters, combined with a metal frame and insulating supports, providing excellent breaking performance. They are suitable for single-phase or two-phase power network systems below 6KV(7.2KV) and 10KV(12KV), allowing for long-distance switching and interruption, frequent starts, and control of resistive, inductive, and capacitive loads. The JCZ1 series single-pole medium-voltage vacuum contactor is commonly used in power protection applications such as signal source arc suppression,....
  • делиться:
  • контакт Онлайн-запрос
  • почтовый ящик:sales@vcbbreaker.com
    WhatsApp:8613736779975

JCZ7(G)12kV 400A Vacuum Contactor

This series of medium-voltage vacuum contactors uses high-quality vacuum interrupters, combined with a metal frame and insulating supports, providing excellent breaking performance. They are suitable for single-phase or two-phase power network systems below 6KV(7.2KV) and 10KV(12KV), allowing for long-distance switching and interruption, frequent starts, and control of resistive, inductive, and capacitive loads. The JCZ1 series single-pole medium-voltage vacuum contactor is commonly used in power protection applications such as signal source arc suppression, harmonic neutral grounding, and load boxes. As a main switch, it features a compact size, fast making and breaking speeds, and strong interruption capacity.


Tech. parameters

Model

160/7.2(12)

250/7.2(12)

400/7.2(12)

630/7.2(12)

800/7.2(12)

Rated voltage of Main Loop 

(KV)

7.2(12)

7.2(12)

7.2(12)

7.2(12)

7.2(12)

Rated current of Main Loop

(A)

160

250

400

630

800

Main loop making capacity

(A/100times)

1600

2500

4000

6300

8000

Main loop switching capability

(A/25times)

1280

2000

3200

5000

6000

Ultimate breaking capacity

(A/3times)

3200

4000

4500

6300

8000

Mechanical life

(10,000 times)

100

100

100

100

100

Electrical endurance AC3

(10,000 times)

25

25

25

25

25

Electrical endurance AC4

(10,000 times)

10

10

10

10

10

Power frequency withstand voltage of main circuit (fracture)

(KV)

32(42)

32(42)

32(42)

32(42)

32(42)

Power frequency withstand voltage of control circuit

(KV)

2

2

2

2

2

Rated operating frequency

(Times/h)

300

300

300

300

300

Clearance between open contacts

(mm)

5(6)±0.5

5(6)±0.5

5(6)±0.5

5(6)±0.5

5(6)±0.5

Overtravel

(mm)

1.5±0.5

1.5±0.5

1.5±0.5

1.5±0.5

1.5±0.5

Secondary control voltage

(V)

AC or DC:110/220/380 or customized

Связанные теги:

Онлайн-сообщение

Пожалуйста, введите действительный адрес электронной почты.
код проверки Не может быть пустым

Связанные продукты

Нет результатов поиска!
Contact Us

Phone: +8613736779975

E-mail: sales@vcbbreaker.com

Address: 66 Punan Road, Yueqing Economic Development Zone, Zhejiang, China

© Yangmei Electric Group, 2025. Все права защищены.

Карта сайта

Этот веб-сайт использует файлы cookie, чтобы обеспечить вам максимально эффективное использование нашего веб-сайта.

Принимать отклонять